VHR network analyser equipment
These devices measure instantaneous physical values of electricity generating and consuming devices and of the electricity transfer and distribution network. High precision measurements are taken throughout a given period. Instantaneous or averaged results can be stored to be used by other systems or for further processing and evaluation.
- Measurement processes are compatible with EN 50160
- 0,1 0,2, 0,5 % accuracy classes
- Current measurement
1/5 A current input
0-2V voltage input - flexible CT
- VT input (e.g. MV level 57 V)
- Adjustable averaging time (1-15 min.)
- Communication methods: RS 232, USB, GPRS
- Long-term registration (1 hour – 90 days)
- Disturbance recorder function
- Provide visual information about the proper equipment
- Metal clamp for positing onto poles
- Encrypted file format
- Calibration certificate
- Common utility software for all types
- Vandal-proof for outdoors and tabletop versions available
The VHR family of devices is so called “network analysers” used for quality control in electrical grids, measuring and evaluating the quality of the received electricity in accordance with the EN 50160 standard.
VERTESZ is undertaking prepaid measurement sessions as well. Please inquire at our regional sales representative!
General features
Input specification:
Periodic input signal,
Nominal frequency: 50 Hz
Isolation strength
2,5 kVeff. 50Hz 1 min.
Voltage input: 0 -230V
Overload: 276V (20%)
current input:
0-1/0-5 A AC, or
1mV/A output clamp, or flexible CT (50A, 100A, 200A, 400A, 800A, 1600A, 3200A)
if VHR-23 is used,
other devices provide a 0-300/0-3000A programmable measurement limit
Accuracy:
Voltage (phase line true RMS value and symmetric components):
0,2% (0,02-1,2 Unominal)
Current RMS value: 0,2% (0,02-1,2 Inominal)
without current sensors
Power factors (P, Q, S), cosφ: 0,5 %
without current sensors
Freqency: 0,1%
Power supply:
Power voltage: supplied from the measured signal, with any phase – 180V AC
Tolerance: 140 – 276 V AC
Power consumptionl: max. 25 VA
Miscallenous specs:
Averaging time: 1-15 minutes
Duration of measurement: 1 hour – 60 days (depending on the type, averaging time and the number of attributes measured)
Mechanical data:
Location of operation can be anywhere
Operation temperature: 0C° – + 60C°
Protection
IP 65 portable vandal-proof outdoor case
IP 50 portable desktop case
IEC 60255 noise protection
Utility software solutions:
Vhr consol – Readout and parametrisation software for VHR devices. It is capable of programming any VHR device. Programming consists of setting the information required for the report: type of measurement instrument, nominal value of current and voltage, the ratio of the current and voltage transformer, location and duration of the measurement, the name of the user, averaging time, etc. Readout of the result is via Vhr consol as well.
Reginfo –automatic measurement controller and integrated evaluation software. It is absolutely essential when using several VHR devices. The software makes instrument maintenance easier, programming them quicker, and it can also automatise processing and evaluating measurement results based on user-defined criteria.
FA phase identifier (pair of devices)
165x82x30mm
(without antenna and cable)
IP40 ■ 0…+50 C°
Application:
The pair of FA-TX and FA-RX devices can be used to take measurement at various supply and consumption points of the given segment of a network …
- Establishing relative phase order
- Determining the angular position between phases
- Identifying phases compared to the reference poin
- Identifying the zero current wire
- Determining GPS coordinates
Power supply:
FA-RX: 9V DC (battery)
FA-TX: 70-265V AC
Range:
1000…2500m
depending on the geographic location and the type of antennae used
For identifying phases at supply and consumption points, compared to the reference junction.
The device uses the open RF band at 868 MHz frequency to communicate via radio. This frequency is available for use. The result of the measurements are displayed by LEDs and an LCD display.
Overload capacity: 400Vac ■ Measurement error: 1° ■ Low energy consumption ■ Light-weight and portable design ■ Huge range
VERTESZ Register Instruments
Types Measured parameters | VHR21 | VHR22 | VHR23 | VHR22K5 | VHR23K5 | VBR6 | |
Voltage parameters | Phase voltages | * | * | * | * | * | * |
---|---|---|---|---|---|---|---|
Line voltages | * | * | * | * | * | * | |
U0measuring or calculation1 | C | M/C | M/C | M/C | M/C | M/C | |
Symmetric components | * | * | * | * | * | * | |
Harmonic components (up to 40th.) | * | * | * | * | * | ||
Phase voltges THD | * | * | * | * | * | ||
Fast transients | * | * | * | * | * | * | |
Phase events reg. | *3 | * | * | * | * | * | |
Short time flicker | * | * | * | * | * | ||
Long time flicker | * | * | * | * | * | ||
Currents | Phase currents | * | * | * | * | ||
I0measuring or calculation2 | M | M/C | M/C | M/C | |||
Symmetric components | * | * | * | ||||
Harmonic components (up to 40th.) | * | * | * | ||||
Phese currents THD | * | * | * | ||||
Phease currents peak factor | * | * | * | ||||
Powers | Active powers(P1, P2, P3, P0) | * | * | * | * | ||
Reactive powers (Q1, Q2, Q3, Q0) | * | * | * | * | |||
Nominal powers (S1, S2,S3, S0) | * | * | * | * | |||
Power factors (PF1, PF2, PF3, PF0) | * | * | * | * | |||
Frequency measurement | * | * | * | * | * | ||
Waveform recording | * | * | * | * | * | ||
Min./max. registry | * | * | * | * | * | * | |
Phase voltage min/max time | * | * | * | * | * | * | |
Phase current min/max time | * | * | * | * | * | * | |
Actual values displaying | * | * | * | * | * | ||
Netwotk type setting4 | * | * | * | * | * | ||
VHR KonzolPro, Reginfo compatibility | * | * | * | * | * | * | |
Inputs | Number of voltage channels | 3 | 3 v 4 | 3 v 4 | 3or 4 by voltage tr. 57 VAC, 100 VAC” | 3or 4 by voltage tr. 57 VAC, 100 VAC” | 3 v 4 |
Number of current channels | 4×4 clamps (300-1000 A) flexibile current tr. (300-3000 A)” | 4×4 clamps (300-1000 A) flexibile current tr. (300-3000 A)” | 4×4 flexibile current tr. (300-3000 A)” | 4×4 clamps (300-1000 A) flexibile current tr. (300-3000 A)” | |||
Data reading | At the end of rec. period | During rec. | During rec. | During rec. | During rec. | During rec. | |
Communication type | RS232, GPRS | USB, GPRS, LAN | USB, GPRS, LAN | USB, GPRS, LAN | USB, GPRS, LAN | USB, GPRS, LAN | |
Protection | IP65 outdoor, UV protected | IP65 outdoor, UV protected | IP65 outdoor, UV protected | IP65 outdoor, UV protected | IP65 outdoor, UV protected | IP65 outdoor, UV protected | |
Others | waveform rec. 3 or 4 voltage and current channels | waveform rec. 3 or 4 voltage and current channels | waveform rec. 3 or 4 voltage and current channels | waveform rec. 3 or 4 voltage and current channels | waveform rec. 3 or 4 voltage and current channels |
Remarks
- U0 measured = M, U0 calculated = Sz
- I0 measured = M, I0 calculated = Sz
- VHR21 voltage event ranges can’t be set
- 0 line yes/no
- Measuring of MV network
- Mesuring for PV power staions supplying points, 3 (4) voltage, 3 (4) current inputs